LV Feeder / Starter Checklist

  1. Check name plate, labelling, ID tags and warning signs correct to drawings / data sheets.
  2. Confirm no mechanical damage and paintwork unmarked.
  3. Confirm that cubicle doors are free from obstruction and no damage to door or seals.
  4. All covers fitted and no fasteners missing.
  5. Plug-in withdrawable functional unit operates correctly in all positions.
  6. Confirm rating of protective devices is as per drawing.
  7. Main and auxiliary contacts on plug-in withdrawable functional unit alignment correct.
  8. Isolator interlocked with door.
  9. Isolator operates correctly.
  10. Selector switches, MCBs and push-buttons are correct to drawing and undamaged.
  11. Instruments and indication lamps correct to drawing and undamaged.
  12. CTs and VTs correct to drawings and undamaged.
  13. Padlocking facilities correct.
  14. Phase identification correct and visible.
  15. Check internals for cleanliness and transit items removed.
  16. Check protection of live parts (busbars / spouts, barriers, etc.) are installed and complete.
  17. All internal wiring / cabling neat and in accordance with drawings and undamaged.
  18. Confirm manufacturers recommended preservation has been conducted.
  19. Measure and record earth resistance from cubicle to main earth point (_________________ Ω).
  20. Installation drawings have been “Red Lined” as per the Project Completions Procedure.

keywords: checklist, LV system, oil & gas project, electrical